200-510-076-114 MPC4 is equipped with 4 dynamic signal channels and 2 speed channels, which can accept signal inputs from various types of sensors such as acceleration, velocity, and displacement. Through these channels, the device can collect various vibration signals and speed signals generated by the mechanical system during operation in real time, thus providing a data basis for subsequent analysis and processing.
The workflow of 200-510-076-114 MPC4 is as follows:
--Receive signals from sensors (such as eddy current probes, accelerometers)
--Perform analog signal conditioning
--Convert to digital signals
--Conduct real-time analysis using DSP
--Compare with the set threshold
--Output alarm or trip signals
Support multiple types of industrial sensors:
--Electromagnetic eddy current displacement probe (Proximity)
--IEPE accelerometer
--Speed sensor
--Magnetic-electric rotational speed probe
--TTL rotational speed signal
| Technical Specifications | |
|
Model |
MPC4 |
|
Part Number |
200-510-076-114 |
|
Description |
Machinery protection card |
| Input channel | 4 channels of dynamics + 2 channels of speed adjustment |
| Frequency range | 0.5 Hz – 20 kHz |
| Response time | <15 ms |
|
Origin |
Switzerland |
|
Dimension |
26*16*5cm |
|
Weight |
0.56kg |
Complementary products and usage suggestions

Recommended complementary modules
VM600 Rack (6U / ABE040 * ABE042)
Power module (such as RPS6U)
CPU/Communication module
I/O module (such as IOC4T)
Sensors (such as eddy current, accelerometer, etc.)
Installation recommendations
-Install the module into the rack
Insert the MPC4 into the slot of the VM600 rack
Make sure it is fully inserted into the backplane connector
Fasten the panel screws
-Connect the sensor
MPC4 supports multiple sensor inputs:
Electromagnetic eddy current probe (shaft vibration/displacement)
IEPE accelerometer (container vibration)
Speed probe (Keyphasor)
-Connect the output to the control system
MPC4 can output:
Relay alarm signal (Alert / Danger)
Analog output (4–20mA / 0–10V)
Communication data (VM-Bus → CPU → DCS)
-Software configuration: The configuration is carried out using the VM600-specific software (such as MPSx):
The configuration content includes:
1️⃣ Select the measurement type
Axis vibration (Radial Vibration)
Axial displacement (Axial Position)
Casing vibration (Casing Vibration)
Speed
2️⃣ Set parameters
Sensitivity (e.g., mV/μm)
Unit (mm/s, μm, g)
Filter range
--System debugging and operation
Power-on inspection of LED status
Check if sensor signals are normal
Calibrate measurement values
Test alarm points
Verify trip logic
The following are some application cases of 200-510-076-114 MPC4 products in different industries
Thermal power plants
Hydropower plant
Aviation parts manufacturing