GSI127 244-127-000-017 A2-B02 Galvanic Separation Unit

GSI127 244-127-000-017 A2-B02 Galvanic Separation Unit

Item Number:GSI127 244-127-000-017
Price: $2500
Lead Time: In stock
Condition: New
Payment: T/T
Shipping Port: Fujian, China
Send Inquiry
Description
Technical Parameters

The GSI127 244-127-000-017 A2-B02 is a galvanic separation unit designed for industrial vibration monitoring and signal transmission applications. It is commonly used in Vibro-Meter monitoring systems to provide electrical isolation between sensors and monitoring equipment.

The unit supports reliable signal conditioning and helps reduce electrical noise interference in critical rotating machinery monitoring environments.

It is recommended that the purchaser confirm the photos of the nameplate, packaging, and label information before making the purchase.
For projects that require bundled procurement, we will also simultaneously check the related monitoring chain products, including signal regulators, vibration probes, extension cables, and monitoring modules, to confirm the corresponding relationships between the models and reduce the occurrence of interface mismatch issues during on-site installation.

product-530-397
Parameter Details
Model GSI127
Part Number 244-127-000-017 A2-B02
Description Galvanic Separation Unit
Origin Switzerland
Dimension 15 × 15 × 5 cm
Weight 0.25 kg
HS code 9022909090
Mounting Type DIN Rail
Application Vibration Monitoring System

 

Products Description

 

The GSI127 galvanic separation unit is a versatile unit that is used for the transmission of high-frequency AC signals over long distances in measurement chains using current-signal transmission, or as a safety barrier unit in measurement chains using voltage-signal transmission. More generally, it may be used to supply any electronic system (sensor side) with a current draw of up to 22 mA.

 

Compatible Vibro-Meter Products:

IPC707 signal conditioners

IQS series signal conditioners

TQ series proximity sensors

CE series accelerometers

VE210 velocity sensors

 

Include the IPC707 signal conditioners (charge amplifiers) used by CAxxx piezoelectric accelerometers and CPxxx dynamic pressure sensors (and older IPC704 signal conditioners too), the IQS9xx signal conditioners used by TQ9xx proximity sensors (and older IQS4xx signal conditioners too), the attached or integrated electronics used by CExxx piezoelectric accelerometers, and the integrated electronics used by the VE210 velocity sensor. The GSI127 is also compatible with industry standard IEPE (integrated electronics piezo electric) vibration sensors, that is, the integrated electronics used by constant-current output sensors such as the CE620 and PV660 (and older CE680, CE,110I, and PV102 sensors too).

 

Signal Isolation and Monitoring Interface Structure

 

GSI127 244-127-000-017 A2-B02 can be connected to IEPE vibration sensors, signal regulators, and monitoring racks and other system structures. In multi-channel monitoring environments, it performs electrical separation between the input and output ends, reducing coupling interference between channels. For industrial sites with many distributed measurement points, the isolation structure helps maintain the signal independence between each monitoring point.

 

GSI127 244-127-000-017 ViewGSI127 244-127-000-0172 adopts a compact structure design, with dimensions of 15 × 15 × 5 cm. It is suitable for installation on DIN rails inside control cabinets. With a weight of 0.25 kg, it has a relatively small impact on the mechanical load of the rails and terminal blocks when multiple modules are combined for installation, making it convenient for combined layout with vibration monitoring modules, interface units, and PLC control components.

 

In long-distance analog signal transmission scenarios, the isolation unit is usually placed between the sensor and the data acquisition system, serving to reduce the effects of common-mode interference, power noise, and grounding circuits on the vibration signal. This type of structure is commonly found in turbine protection systems, compressor monitoring systems, oil and gas processing equipment, and industrial process automation control cabinets.

 

ORDERING INFORMATION

 

Type GSI127
Designation Galvanic separation unit
Part number (PNR) 244-127-000-017
--A(Environment) Standard 1  
Explosive (Ex) 2  
     
--B Sensitivity Zero Description
1 V/mA 5 mA → 7 V For CExxx with a current output
1 V/mA 12 mA → 7 V
13 mA → 8 V
For IPCxxx or VE210 with a
current output2
3.2 V/mA 15 mA → 0 V For IQSxxx with a current output
1 V/V --- For IPCxxx with a voltage output
−1 V/V --- For IQSxxx or VE210 with a
voltage output
1 V/V --- For industry standard IEPE
(integrated electronics piezo electric)
vibration sensors

 

FAQ

Q: Is GSI127 244-127-000-017 still available?

A: Yes, stock availability depends on current inventory status.

Q: Does the product come with the original factory label and nameplate?

A: The inventory products usually retain the original labels, serial numbers and nameplates.

Q: Is GSI127 applicable to the turbine monitoring system?

A: This Galvanic Separation Unit is commonly used in vibration signal isolation and interface connection systems of rotating machinery such as steam turbines, compressors, and generator sets.

Q: Could you please provide the product photos and the packaging photos?

A: Before shipment, we can provide customers with actual photos of the product, the label design, and the packaging illustration for their confirmation.

 

product-930-698
Why Customers Source GSI127 From Us

 Independent testing before shipment

 Anti-static industrial packaging

 Global shipping support

 Fast response for RFQ requests

 Support for obsolete automation parts

 Export experience in industrial control systems

 

PDF Datasheet Download

 

 

 

 

 

 

 

 

 

Hot Tags: 244-127-000-017, GSI127 244-127-000-017, 244-127-000-017 A2-B02, Galvanic Separation Unit, Vibro-Meter GSI127, monitor system module, 200-582-993-022, 200 582 993 022 Rack Power Backplane, Power Backplane 200 582 993 022