Product Introduction

Technical Specifications
|
Manufacture |
General Electric(GE) |
|
Model |
IC698PSA100 |
| Part Number | IC698PSA100 |
|
Description |
PACSystems™ RX7I Power Supply Module |
|
Origin |
USA |
|
Dimension |
30*25*8cm |
|
Weight |
2kg |
Product Details
IC698PSA100: Provides up to 100 W total output power at ambient temperatures of 0 to 60ºC without forced air cooling.
Output voltages: +5 VDC output up to 20 amps
+12 VDC output up to 2 amps
–12 VDC output up to 1 amp
The PACSystems* RX7i power supplies provide +5 VDC, +12 VDC, and -12 VDC power, logic-level sequencing signals to modules on the RX7i backplane. The Power Supply Module plugs directly into slot 0 in the RX7i main rack.
The power supply output can ride through the loss of up to one AC input line cycle without loss of output power. Protection is provided for overcurrent, overtemperature, and overvoltage fault conditions.
Features:
■ Operation from 85 to 264 VAC, 100 to 150 VDC
■ Slide-in rack mount construction
■ Electronic short circuit overcurrent protection
■ Overcurrent and overvoltage fault protection
■ Power factor correction for AC operation
Release History:
| Version | Date | Comments |
| PSA100E | Aug 2010 | Label change only. No change in functionality, performance, or compatibility. |
| PSA100D | Aug 2006 |
Power supplies qualified to the Explosive Atmospheres Directive, European Safety for Hazardous Locations, Equipment Group II, Category 3 (ATEX) agency standard. Corrected an infrequently observed issue with the power supply shutdown, causing corrupted memory faults in the CPU. |
| PSA100C | Jun 2005 | Overtemperature detection. See GFK-2237C for details. |
| PSA100B | May 2004 | See GFK-2237B for details. |
| PSA100A | May 2003 | Initial release. |
Power Supply Operation:
The two-position On/Off switch, located on the front faceplate, is a logic-level switch that enables or disables the output channels only. This switch does not interrupt the AC line input.
The ACFAIL# signal is pulled down when the power supply inputs are no longer being provided or when the ON/OFF switch is OFF. The ACFAIL# signal is asserted at least 5ms before outputs fall below their specified limits to provide sufficient warning to the system of a power failure.
The RX7i power supplies do not drive the SYSRESET# signal on the VME backplane. The RX7i CPU module controls the SYSRESET# signal.
To avail our best deals for IC698PSA100, contact us and we will get back to you within 24 hours.