Product Introduction

Technical Specifications
|
Manufacture |
General Electric(GE) |
|
Model |
IC698PSA350 |
| Part Number | IC698PSA350 |
|
Description |
PACSystems™ RX7I Power Supply Module |
|
Origin |
USA |
|
Dimension |
30*25*8cm |
|
Weight |
2kg |
Product Details
IC698PSA350: Provides up to 350 W total output power; requires forced air cooling, provided by a fan tray mounted on the bottom of the rack.
Output voltages: +5 VDC output up to 60 amps
+12 VDC output up to 12 amps
–12 VDC output up to 4 amps
The following LED indicators are provided on the power supply front panel.:
| LED Name | Color | Function |
| FIELD OK | green | Turns ON when AC power is applied within its specification range. |
| OUTPUT OK | green |
Turns ON when all three DC output channels are operating within their specifications. Turns OFF if any of the three DC output channels have failed. |
| OVER TEMP IC698PSA350 only | red | Turns ON if the critical supply temperature is exceeded or if the airflow sensor detects cessation of air flow. |
Any output channel that exceeds the nominal output voltage by 15% or more will cause all outputs to latch off. The ON/OFF control switch or the AC input power must be recycled to reset.
The IC698PSA350 power supply is capable of operating at full capacity (350W) from 0 to 60ºC with 70 CFM forced air cooling provided by a fan tray mounted below the system chassis. This power supply can operate at a limited capacity with only convection cooling.
Both RX7i power supplies have internal temperature sensing that shuts down the output channels if overheated. Recovery is automatic when the internal temperature returns to the specified operating range. The IC698PSA350 power supply has an OVER TEMP indicator that comes on when the output channels become overheated.
An airflow sensor is provided in the IC698PSA350 power supply to detect a fan failure or air blockage. If the power supply senses a cessation of airflow, it responds by latching off all outputs and turning on the overtemperature LED indicator. A power cycle is required to recover from this latched condition.
All outputs are protected against overcurrent and short circuit with automatic recovery upon removal of the fault.
An electronic current limit is provided on each of the three outputs. An overload on any output will cause the voltage to collapse and may cause the other output voltages to collapse.
Normal operation will resume after removal of the overload. Some component cooling time may be required before normal operation resumes.
Ordering Information:
RX7i Power Supply: 85 to 264 VAC at 47 to 63 Hz, 125 VDC Input, 100-watt output IC698PSA100
RX7i Power Supply: 85 to 264 VAC at 47 to 63 Hz, 125 VDC Input, 350-watt output IC698PSA350
120 VAC Input Rack Fan Assembly for 17-Slot Rack IC697ACC721
240 VAC Input Rack Fan Assembly for 17-Slot Rack IC697ACC724
24 VDC Input Rack Fan Assembly for 17-Slot Rack IC697ACC744
120 VAC Input Rack Fan Assembly for 9-Slot Rack IC697ACC621
240 VAC Input Rack Fan Assembly for 9-Slot Rack IC697ACC624
24 VDC Input Rack Fan Assembly for 9-Slot Rack IC697ACC644
To avail our best deals for IC698PSA350, contact us and we will get back to you within 24 hours.