IC694ALG392 8-Channel Analog Current Voltage Output module provides up to eight single-ended output channels with current or voltage outputs. Each analog output channel is capable of providing two current output ranges or two voltage output ranges. Each channel can be individually configured for the output range required for your application. The module no jumpers or switches for configuration.
All ranges can be configured using either the Logicmaster 90-30/20/Micro configurator function or the ClMPLICITY Control Programming Software configurator function, or the Series 90-30 Hand-Held Programmer. The default range is 0 to +10 volts. Configurable current and voltage output ranges are.

Technical Specifications
|
Manufacture |
GE |
|
Model |
IC694ALG392 |
| Part Number | IC694ALG392 |
|
Description |
Analog Output Module |
|
Origin |
USA |
|
Dimension |
30*25*5cm |
|
Weight |
0.55kg |
Product Details
IC693ALG392 Each channel is capable of converting 15 to 16 bits (depending on the range selected) of binary(digital) data to an analog output for use as required by your application. All eight channels are updated every 12 milliseconds. User data in the %A0 registers is in a 16-bit 2's complementfomat. In current modes, an open-wire fault is reported to the CPU for each channel. The module can go to the known last state when the system power is interrupted. As long as user power is applied to the module, each output will maintain its last value, or reset to zero, as determined by how you have configured the module.
Important Product Information
Please note the following important product information. This version of the 8-Channel Analog Current/Voltage Output module requires the following product versions for compatibility:
CPU: Firmware Versions 3.3 to 4.6:
If your CPU has a firmware version 3.3 to 4.6. You must select 16 %lbits at configuration. If this selection is not made. A loss of module fault will occur.
CPU: Firmware Version 5.0 or later: If your CPU has firmware version 5 or later, then the %Iconfiguration will accept 8 or 16 %I bits.
Logicmaster 90-30/20/Micro Software: Version 5.00 or later is required to configure the module using the Logicmaster 90-30/20/Micro software configuration function.
Control Software: Version 2, or llater is required to configure the module using the Control Software configuration function.
IC693ALG392 Power Requirements and LEDs
This module requires a maximum of 110 mA from the 5V bus on the PLC backplane for the
logic side The module's analog power must be supplied by a user-supplied single +24 VDC
power source and requires a maximum current of 315 mA.
There are two green LED indicators on the module, which provide module and user supply
status. The top LED, OK, provides module status information ,and the bottom LED, USOK,
indicates whether the user supply is present and is above a minimum designated level. Note
that both LEDs are powered from the +5V backplane power bus.
Location in System
This module can be installed in any 1/0 slot of a 5 or 10-slot baseplate in a Series 90-3PLC system
References Used
The number of 8-Channel Analog Current/Voltage Output modules that may be installed in a system depends on the amount of %AQ and %I references available. Each module uses 8 %AQ references (depending on the number of channels enabled) and 8 or 16 %I references (depending openwire detect configuration).
There are 32 %AQ references available in a Model 311, Model 313, and Model 323 system, 64%AQ references available in a Model 331 system, 256 %AQ references available in a Model 340 and Model 341 system, and 512 % AQ references available in a Model 35l and Model 352 system.m
The maximum number of 8-Channel Analog Current/Voltage Output modules that can be installed in asysteme:
4 in a system using CPU Models 311, 313, or 323
8 in a system using CPU Model 331
32 in a system using CPU Models 340 and 341
64 in a system using CPU Models 350-364
Other Configuration Considerations
When planning the module configuration for your apapplicationyou must also consider the load capacity of the installed power supply and the total load requirements of all modules that are installed in the baseplate.
Refer to Chapter 1 in this manual for details on power supply, baseplate, and module load requirements. The following table lists the specifications for this module. Note that test conditions, unless otherwise noted, are: VusER = 24 VDC at an ambient temperature of 25 °C (77° F).