Product Introduction
Emerson A6370D is a high-performance overspeed protection monitor, which is part of the Emerson AMS 6300 SIS overspeed protection system. It is mainly used to monitor the speed of rotating machinery (such as turbines, compressors, etc.). Once the speed exceeds the set value, an alarm signal will be issued and corresponding protective measures will be taken to prevent equipment damage.

Technical Specifications
|
Manufacture |
EMERSON |
|
Model |
A6370D |
|
Part Number |
A6370D |
|
Description |
Overspeed Protection Monitor |
|
MoOrigin |
Germany |
|
Dimension |
34*17*6cm |
|
Weight |
0.43kg |
Product Details
The A6370 Monitor is part of the AMS 6300 SIS Overspeed protection system and is mounted in a 19" rack (84HP width and 3RU height) in combination with the A6371 system backplane. One AMS 6300 SIS consists of three Protection monitors (A6370) and one backplane (A6371). The system is designed for use with Eddy-Current sensors, Hall- Element sensors and Magnetic (VR) Sensors.
| Sensor Voltage Supply | ||
| Nominal Supply Voltage | -24.5 V ±1.5V DC | Short-circuit proof, galvanically separated |
| Max. Current | 35 mA | |
| Signal Input, Eddy Current & Hall Element Sensors | ||
| Input Signal Voltage Range | 0 V to 26 V (+/-) | Protected against reverse polarity |
| Limit Range | ± 48 V | |
| Frequency Range | 0 to 20 kHz | |
| Input Resistance | Typical 100 kΩ | |
| Signal Input, Magnetic (VR) Sensors | ||
| Input Signal Voltage Range | Min. 1 Vpp, max. 30 V RMS | |
| Frequency Range | 0 to 20 kHz | |
| Input Resistance | Typical 18 kΩ | |
| Digital Input (Backplane) | ||
| Number of Inputs | 4 (Galvanically separated with common ground of all digital inputs) | (Test Value 1, Test Value 2, Enable Test Values, Reset Latch) |
| Logic Low Level | 0 V to 5 V | |
| Logic High Level | 13 V to 31 V, open | |
| Input Resistance | Typical 6.8 kΩ | |
| Current Output (Backplane) | ||
| Number of Outputs | 2 | Electrically isolated with common ground |
| Range | 0/4 to 20 mA or 20 to 4/0 mA | |
| Accuracy | ±1% of full scale | |
| Maximum Load | <500 Ω | |
| Max. Output Current | 20 mA | |
| Digital Output (Backplane) | ||
| Number of Outputs | 3 | Open-Collector-Emitter, Current limited, galvanically separated |
| Max. Voltage | 31.2 V | |
| Max. Current | 16 mA @ 24 V | |
| Frequency Range | 0 to 20 kHz | |
| Pulse Output (Front Panel) | ||
| Number of Outputs | 1 (Short-circuit-proof) | |
| Voltage | 0 to 5 V | TTL- Signal |
| Frequency Range | 0 to 20 kHz | |
| Output Impedance | Typical 10 kΩ | |
| Sens. Output (Front Panel) | ||
| Number of Outputs | 1 (Short-circuit-proof) | |
| Voltage | 0 to 3.9 V | Factor 0.15 ± 3% |
| Frequency Range | 0 to 20 kHz | |
| Output Impedance | Typical 10 kΩ | |
| Communication | ||
| USB | Configuration Interface, USB type B | |
| RS 485 |
Max. 32 devices Baud Rate: 38400, 57600,115200 Baud |
|
| Profibus DP (A6370D/DP only) |
Max. 31 devices Data transmission rate: up to 12 Mbit/s |
|
| Reaction Time | ||
| Speed | < Measuring Time + 8 ms | |
| Typical Reaction Time Speed at 3000 min-1 |
Mode "1x per revolution": 35 ms Mode "Automatically": 12.5ms |
|
| Rotational Direction | < 3 * Period time of input signal + 8 ms |
FAQ
Q: Do you have the products in stock?
A: We keep most models in stock, but our inventory is updated daily. Please contact us if you need to verify the availability of any products.
Q: What about transportation?
A: Typically, we use air freight because it is more convenient and faster.
Q: Do you offer after-sales service?
A: Yes, we provide excellent after-sales service, addressing customer complaints and resolving issues for our clients.