Product Introduction
The 3500/23E Transient Data Interface (TDI) is the interface between the 3500 ENCORE monitoring system and GE's System 1* condition monitoring and diagnostic software. The TDI combines the capability of a System Monitor with the data collection capability of a communication processor.
Technical Specifications
|
Manufacture |
BENTLY NEVADA |
|
Model |
3500/23E |
|
Part Number |
285690-01 |
|
Description |
Transient Data Interface |
|
Origin |
USA |
|
Dimension |
30*23*5cm |
|
Weight |
1.45kg |
Product Details
The 3500/23E 285690-01 TDI operates in the System Monitor slot of a 3500 ENCORE rack, in conjunction with the vibration monitors (3500/42E), to continuously collect steady-state and transient waveform data and pass this data through an Ethernet link to the host software. Static data capture is standard with the TDI; however, using an optional Channel Enabling Disk will also enable the TDI to capture dynamic or transient data. The TDI features improvements in several areas over previous communication processors and incorporates the Communication Processor function within the 3500 ENCORE rack.
The TDI module provides extensive communication capabilities of all rack monitored values and statuses for integration with process control and other automation systems using serial (RS232/RS422/RS485) communications capabilities.
Every 3500 ENCORE rack requires one TDI, which always occupies Slot 1 (next to the power supplies).

Front Panel:
LEDs:
Rack OK LED: Indicates when the 3500 ENCORE System is operating properly
TDI OK LE D: Indicates when the 3500/23E is operating properly
TM L ED: Indicates when the 3500 ENCORE System is in Trip Multiply mode.
CONFIG OK LED: Indicates that the 3500 ENCORE System has a valid configuration.
I/O Module OK Relay: Relay to indicate when the 3500 ENCORE System is operating normally or when a fault has been detected within the system. The user can select either an "OPEN" or "CLOSED" contact to annunciate a NOT OK condition. This relay always operates as "Normally Energized".
OK Relay: Specifications in 3300/12 or 3300/14 data sheet
Rack reset button: Clears latched alarms and Timed OK Channel Defeat in the rack.
Perform the same function as the "Rack Reset" contact on the I/O module.
Display Control switches: Used to control all of the displays of the monitors in the rack.
Hom: Used to return all of the monitor displays to their primary screen.
Page Up: Moves all displays to their next screen.
Page Down: M Moves all displays to their previous screen.
Note: The Display Control switches are provided to support a future enhancement to the 3500/23E.
Ordering Information:
|
Transient Data Interface 3500/23E-AXX-BXX |
|||
| A:I/O Module Type | |||
| 0None | nejust the current installed 3300 PIM. | ||
| B: Agency Approval Option | |||
| 0 0 | None | ||
| 0 1 | CSA/NRTL/C (Class 1, Div 2) | ||
Note: For installation as a retrofit monitor for a 3300 System, Agency Approval Option B01 should be ordered only if the existing 3300 System has the same type of approvals. The installation of a retrofit monitor in a system without approvals will invalidate the approvals of the monitor.
Spares:
| 285690-01 | 3500/23E TDI |
| 287545-01 | 3500/23E Monitor Manual |