Product Introduction
Woodward 8200-1301 is a 505 Series digital governor used to control industrial steam turbines, small grid turbo generators or turbo expanders. It can be used with stratified steam inlet valve actuators and is suitable for steam turbine control of various structural sizes.

Technical Specifications
|
Brand |
WOODWARD |
|
Model |
8200-1302 |
| Part Number | 8200-1302 |
|
Description |
505 Digital Control for Steam Turbines |
|
Origin |
USA |
|
Dimension |
35*30*20cm |
|
Weight |
1.52kg |
Product Details
8200-1302 Flex505 controller is a significant upgrade to the existing 505 product line with enhanced CPU, Graphical display, communications, and I/O functions.
Features:
Same installation/mounting as current 505
8.4" LCD Display (800x600) and Keypad
(LV) input power: 18-36 Vdc input, isolated
(HV) input power: 88-264 Vac / 90-150 Vdc, isolated
Operating range of –30 °C to +70 °C (with display)
Communications:
(4) Ethernet 10/100 communication ports, isolated
(4) CAN communication ports (1 Mbit), isolated
(1) RS-232/RS-485 port, isolated
(1) RS-232 Service port, isolated
I/O circuits:
GAP configurable update rates of 5 ms to 160 ms
(2) Speed Sensor inputs (MPU/Prox) (with Prox Power)
(8) Analog input 4-20 mA channels (with Loop Power)
(6) Analog output 4-20 mA channels
(2) Actuator output channels (configurable 4-20 mA/20-200 mA)
(20) Discrete input channels (with Contact Power)
(8) Relay outputs (form-c)
Environmental Specifications:
| Operating Temperature | –30 °C to +70 °C (with display) |
| Storage Temperature | –30 °C to +70 °C (recommended 0 °C to 40 °C) |
| Vibration | 8.2 Grms, industrial skid mount, per Woodward RV1 |
| Shock1 | 10 G, 3x each axis, per Woodward MS1 procedure |
| Humidity2 | 5 % to 95 %, non-condensing |
| Ingress Rating / Installation3 | IP20, Pollution Degree2, Overvoltage Category 3 |
| EMC Emissions4 |
EN 61000-6-4 (Heavy Industrial) IACS UR E10 (Commercial Marine) |
| EMC Immunity4 |
EN 61000-6-2 (Heavy Industrial) IACS UR E10 (Commercial Marine) |