Setting Speed Range
The speed range to be selected is determined by the maximum desired prime mover speed. Calculate the frequency of the speed sensor signal at the maximum prime mover speed by multiplying the gear speed in revolutions per minute times the number of teeth on the speed sensing gear and dividing by 60. Select the lowest speed range which contains this maximum speed sensor frequency.
Potential Transformer Connections
Connect the potential transformer secondary leads to the following terminals:
Phase A to terminal 1
Phase B to terminal 2
Phase C to terminal 3
The potential transformer secondary line-to-line voltage must be in the 90 to 240 Vrms range. Refer to the plant wiring diagram.
Current Transformer Connections
The standard method of connecting the current transformers is shown in the plant wiring diagram. An alternate method is the open delta connection shown in the insert in the plant wiring diagram.