Description
Technical Parameters
Technical Specifications
|
Brand |
HIMA |
|
Model |
F6103 |
|
PN Number |
F6103 |
|
Description |
Terminal Blocks |
|
Origin |
Germany |
|
Dimension |
14*14*4m |
|
Weight |
0.15kg |
Product Details
F6103 belongs to the HIMA HIQuad X series.
The H51X system family has a modular structure which includes an H51X base rack and up to 16 extension racks. The H51X base rack (F-BASE RACK 01) can be equipped.
The communication modules are connected to the processor modules via two system buses (A and B) in a point-to-point connection. The processor module in slot 8 controls and monitors system bus A whereas the processor module in slot 10 controls and monitors system bus B.During redundant operation, the two processor modules align their data.
The RJ-45 interfaces on the rear side of the base rack are used to connect the extension racks to the processor modules. An I/O processing module (F-IOP 01) must be used in the extension rack to connect the system buses to the I/O bus.

Thanks to the use of safety-related modules (I/O modules, the I/O processing module and a processor module), the HIQuad H51X system can ensure safety-related signal processing in accordance with SIL 3 already when operating in a mono structure.
The input modules of the HIQuad H51X system safely record the values measured by sensors.Data is exchanged with the processor module via the I/O processing module. The measured values are cyclically queried by the processor module and processed by the user program. The user program's results are sent to the I/O processing module, which writes them to the output modules. The output modules thus control the field level, e.g., the actuators.
During mono operation, the signal is forwarded by the processor module in slot 8 via system bus A.
the example of an H51X mono system with system bus A. Up to 16 extension racks can be connected to the system bus in any UP loop, DOWN loop, or UP and DOWN loop. The extension racks are interconnected with system bus A via the I/O processing module, see the F-IOP 01 manual (HI 803 219 E).
If the system bus connection is interrupted in a mono system, all I/O modules located after the interruption point are no longer available. After the interruption point, all output modules enter the safety-related, de-energized state. As for the input modules, the failsafe initial values are processed in the respective processor module.
RELATED PRODUCTS
| HIMA F8640 | HIMA F3221 |
| HIMA F3001 | HIMA F3226 |
| HIMA F3211 | HIMA F3226A |
| HIMA F3246A | HIMA F3236 |
| HIMA F5109B | HIMA F3318 |
| HIMA F6706 | HIMA F3322 |
| HIMA F7113 | HIMA F3330 |
| HIMA F7114 | HIMA F3331 |
| HIMA F7130A | HIMA F3332 |
| HIMA F7132 | HIMA F3414 |
| HIMA F7529 | HIMA F6214 |