Description
Technical Parameters
Product Introduction
IS215UCVDH5A is a VME controller of GE MKVI series.The IS215UCVDH5A is a double-slot board using a 300 MHz AMD K6 processor with 8 MB of flash memory and 16 MB of DRAM. A single 10BaseT (RJ-45 connector) Ethernet port provides connectivity to the UDH.
Technical Specifications
|
Manufacture |
General Electric(GE) |
|
Model |
IS215UCVDH5A |
| Part Number | IS215UCVDH5AN |
|
Description |
Mark VI UCVD Controller
|
|
Origin |
USA |
|
Dimension |
30*20*6cm |
|
Weight |
0.35kg |
Product Details
The UCVD contains a double column of eight status LEDs. These LEDs are sequentially turned on in a rotating pattern when the controller is operating normally. When an error condition occurs, the LEDs display a flashing error code that identifies the problem.

UCVD Controller Specifications
|
Item
|
Specification
|
|
Microprocessor
|
MD-K6 300 MHz
|
|
Memory
|
16 MB DRAM
8 MB Flash Memory in UCVD
256 KB of level 2 cache
|
|
Operating System
|
QNX
|
|
LEDs
|
LEDs on the faceplate provide status information as follows:
ACTIVE Processor is active
SLOT 1 Controller configured as slot 1 controller in VME rack
BMAS VME master access is occurring
ENET Ethernet activity
BSLV VME slave access is occurring
STATUS Display rotating LED pattern when OK.
Display flashing error code when faulted
FLSH Writing to Flash memory
GENX Genius I/O is active
|
|
Programming
|
Control block language with analog and discrete blocks; Boolean logic represented in relay ladder diagram format. Supported data types include:
Boolean
16-bit signed integer
32-bit signed integer
32-bit floating point
64-bit floating point
|
|
Ethernet Interface
|
Twisted pair 10BaseT, RJ-45 connector
TCP/IP protocol used for communication between controller and toolbox
Serial Request Transfer Protocol (SRTP) interface between controller and HMI
EGD protocol for communication with CIMPLICITY HMI, and Series 90-70 PLCs
Ethernet Modbus protocol supported for communication between controller and third-party DCS
|
|
COM Ports
|
Two micro-miniature 9-pin D connectors
COM1 Reserved for diagnostics, 9600 baud, 8 data bits, no parity, 1 stop bit
COM2 Used for serial Modbus communication, 9600 or 19200 baud
|
|
Power Requirements
|
+5 V dc, 6 A
+12 V dc, 200 mA
-12 V dc, 200 mA
|