Technical Specifications
|
Manufacture |
General Electric(GE) |
|
Model |
IS220PCLAH1A |
| Part Number | IS220PCLAH1A |
|
Description |
MARK Core analog module |
|
Origin |
USA |
|
Dimension |
30*20*8cm |
|
Weight |
0.35kg |
Product Details
PCLA Core Analog Module - Aero
The following hardware combinations are approved for use in hazardous locations:
• Core analog module IS220PCLAH1A or IS220PCLAH1B
• Terminal board (accessory) IS210SCLSH1A
• Optional terminal board (accessory) IS200SCLTH1A
IS220PCLAH1A features:
Rich signal input and output: Thermocouple input, RTD input, voltage input, and 4-20mA current loop input and output are provided by PCLA and SCLT, which can meet most of the analog signal I/O required for the operation of aero-derivative gas turbines.
Compatible with multiple control systems: It can be used for multiple types of control systems with dual controller TMR I/O, dual controller simplex I/O, simplex controller TMR I/O, and all other Mark VIe I/O packages and controllers can work perfectly with PCLA modules.
Support multiple frame rates: Frame rates of 10, 20, 40, 80, 160 and 320ms are designed to be used with PCLA modules and can be selected according to actual needs.
IS220PCLAH1A hardware structure:
Dual circuit board design: The PCLA module is composed of two different circuit boards: the processor board and the BCLA acquisition board.
Rich interfaces: It has two RJ45 Ethernet interfaces for connecting to the network; it is also equipped with power interfaces, signal input and output interfaces, such as the 96-pin J3 and 48-pin J4 connectors for connecting to the system, and the 68-pin cable for connecting the SCLS and SCLT boards.
LED diagnostic indicators: There are several LED diagnostic indicators on the front panel to display various module fault conditions.
Electrical Ratings:
| Item | Min | Nominal | Max | Units |
|
Power Supply |
||||
| Voltage | 27.4 | 28 | 28.6 | V dc |
| Current | - | - | 0.78 | A dc |
| Analog Inputs | ||||
| Voltage | -10 | - | 10 | V dc |
| Current | 0 | - | 20 | mA dc |
| Thermocouple Inputs | ||||
| Voltage | -16 | - | 63 | mV dc |
| RTD Inputs | ||||
| Voltage | 0 | - | 0.7 | V dc |
| Current | - | 1.0 | - | mA dc |
Submit your inquiry and we will contact you