Product Introduction
VE3008 KJ2005X1-MQ2 is a controller module in the Emerson DeltaV system, specifically an MQ controller. This module is used to provide communication and control functions in the DeltaV system, connecting field devices and other control network nodes. This module is widely used in industrial automation systems that require high reliability and high performance control.

Technical Specifications
|
Manufacture |
EMERSON |
|
Model |
VE3008 |
|
Part Number |
KJ2005X1-MQ2 |
|
Description |
MQ Controller |
|
MoOrigin |
USA |
|
Dimension |
26*16*6cm |
|
Weight |
0.43kg |
Product Details
The MQ Controller facilitates communication and control between field devices and other nodes on the control network. Control strategies and system configurations developed on previous DeltaV™ systems are compatible with this powerful controller. The MQ Controller offers all the features and functions of the MD Plus Controller, including the same memory capacity. The control languages executed in the controllers are detailed in the Configuration Software Suite product data sheet.
VE3008 KJ2005X1-MQ2 has the following features:
| Powerful: Provides the same features as the MD Plus controller, including the same memory capacity. |
| Communication capabilities: Supports multiple communication interfaces, such as Ethernet, to achieve efficient data transmission. |
| Self-positioning and self-identification: With self-positioning function, it is easy to quickly find the physical location of the controller in the system. |
| Automatic I/O detection: Able to automatically identify the I/O interface channels connected to the subsystem. |

Specifications
| Power, Mounting, and Memory |
| VE3008 KJ2005X1-MQ2 |
| Power Requirement | Supplied by System Power Supply through 2-wide Power/Controller Carrier |
| Fuse Protection | 3.0 A, non-replaceable fuses |
| Power Dissipation | 5.0 W typical, 7.0 W maximum |
| Mounting | On right slot of Power/Controller Carrier |
| User Memory | 48 MB |
| Primary Control Network | 8-pin RJ-45 connector |
| Redundant Control Network | 8-pin RJ-45 connector |
| LED Indicators (ON Status) |
| VE3008 KJ2005X1-MQ2 |
| Green – Power | Indicates DC power is applied |
| Red – Error | Indicates an error condition |
| Green – Active | Indicates that the controller is operating as the primary controller |
| Green – Standby | Indicates that the controller is operating as a backup controller (reserved for future use) |
| Yellow Flashing – Pri. CN | Indicates valid primary control network communication |
| Yellow Flashing – Sec. CN | Indicates valid secondary control network communication |
| All except Power flashing | Visual identification of controller initiated from user interface software by ping command |
| All except Power flashing, alternating even and odd | Firmware upgrade in progress |
| Environmental |
| VE3008 KJ2005X1-MQ2 |
| Operating Temperature* | -40° to 70°C (-40° to 158°F) |
| Storage Temperature | -40° to 85°C (-40° to 185°F) |
| Relative Humidity | 5 to 95%, non-condensing |
| Airborne Contaminants | ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating |
| Shock (normal operating conditions) | 10 g ½-sine wave for 11 ms |
| Vibration (operative limit) | 1 mm peak-to-peak from 5 Hz to 16 Hz, 0.5 g from 16 Hz to 150 Hz |