Product Introduction
ABB Bailey IMCIS02 is a high-performance I/O slave module for industrial automation control systems. It is mainly used for signal processing and communication of ABB Bailey Infi 90 and Net 90 systems. It provides 4 analog inputs and 3 digital input channels. It also provides 4 digital outputs and 2 analog output channels.

Technical Specifications
|
Brand |
ABB Bailey |
|
Model |
IMCIS02 |
|
Part Number |
IMCIS02 |
|
Description |
Control I/O Slave Module |
|
Origin |
USA |
|
Dimension |
36*28*8cm |
|
Weight |
0.75kg |
Product Details
OVERVIEW
The Control I/O Slave module (IMCIS02) brings four analog and three digital process field signals into the Infi 90 system for processing and monitoring. It outputs four digital and two analog signals for process control. The Control I/O Slave (CIS) module is an interface between the process and the Infi 90 Process Management System. Master modules perform the control functions; slave modules provide the I/O to the master modules.
This manual explains the purpose, operation and maintenance of the slave module. It addresses handling precautions and installation procedures. Figure 1-1 illustrates the Infi 90 communication levels and the position of the CIS module within these levels.

MODULE DESCRIPTION
The CIS consists of a single printed circuit board (PCB) that occupies one slot in a Module Mounting Unit (MMU). A dipswitch on the PCB configures each of the analog outputs; jumpers configure each of the digital inputs. Each analog input is configured on its respective Termination Unit (TU) or Termination Module (TM).
Two captive screws on the faceplate secure the module to the MMU. A front panel LED indicates the module status.
The slave module has three connection points for external signals and power (P1, P2 and P3). P1 connects to logic power that drives the module circuits (refer to Table 5-2). P2 connects it to the slave expander bus to communicate with a Multi-Function Processor (MFP) module (refer to Table 5-3). The digital and analog signals are input and output through connector P3 using a cable connected to a TU/TM (refer to Table 5-4). The terminal blocks (physical connection points) for field wiring are on the TU/TM.

Specifications
| POWER REQUIREMENTS | |
| Voltage |
+5 VDC (±5%) +15 VDC (-2.5%, +5%) -15 VDC (-5%, +2.5%) +24 VDC (±10%)(from termination unit/termination module) |
| Current (maximum) |
332 mA (+5 VDC) 35 mA (+15 VDC) 30 mA (-15 VDC) 50 mA (+24VDC) |
| Dissipation |
1.65 W @ +5 VDC 525 mW @ +15 VDC 450 mW @ -15 VDC 1.20 W @ +24 VDC |
| DIGITAL I/O | |
| Digital Inputs (3) | Optically isolated |
| Current (typical) |
4.5 mA @ 24 VDC 5.0 mA @ 125 VDC 7.0 mA @ 120 VAC rms @ 60 Hz |
| Voltage |
24 VDC (±10%) 125 VDC (±10%) 120 VAC (±10%) |
|
Turn-On Voltage (minimum) 24 VDC 21.4 VDC 125 VDC 95.0 VDC 120 VAC 85.0 VAC |
|
|
Turn-Off Voltage (maximum) 24 VDC 12 VDC 125 VDC 60 VDC 120 VAC 42 VAC |
|
|
Maximum Input Current at Minimum Turn-On 24 VDC 3 mA @ 21.4 VDC 125 VDC 3 mA @ 95.0 VDC 120 VAC 5 mA @ 85.0 VAC 60 Hz |
|
|
Off Leakage Current (maximum) 24 VDC 10 µA (@ Vin ≤ 12 VDC) 125 VDC 10 µA (@ Vin ≤ 60 VDC) 120 VAC 1.6 mA (@ Vin ≤ 42 VAC 60 Hz) |
|
| Response Time |
DC "Fast" - 1.5 ms DC "Slow" - 17 ms |
| DIGITAL I/O | |
|
Digital Outputs (4) Off Output Voltage On Output Voltage Off Output Current On Output Current |
Open collector, optically isolated VI/O Nominal 24 VDC 2.4 VDC Max 10 µA Max 250 mA Max |
| ANALOG I/O | |
|
Analog Inputs (4) TU/TM configured to accept:
Input Impedance Common Mode Voltage Normal Mode Rejection (minimum) Common Mode Rejection (minimum) |
1 - 5 VDC (differential) Powered or unpowered current (4 - 20 mA) Single-ended or differential voltage (1 - 5 VDC) >1 Mohm ±10 VDC 76 db @ 60 Hz 90 db @ 60 Hz |
|
Analog Outputs (2) Output Load
|
4 - 20 mA or 1 - 5 VDC
600 ohm, 600 millihenries >1 Kohm |
| A/D Resolution | 12 bits for analog inputs |
| D/A Resolution | 10 bits for analog outputs |
| ENVIRONMENTAL | |
| Ambient Temperature | 0o to 70o C (32o to 158o F) |
| Relative Humidity |
0% to 95% up to 55o C (131o F) (non-condensing) 0% to 45% up to 70o C (158o F) (non-condensing) |
| Altitude | Sea Level to 3 Km (1.86 miles) |
| Air Qualit | Non-corrosive |
| CERTIFICATION | |
| CSA certified for use as process control equipment in an ordinary (non-hazardous) location. | |